Commercial kitchen exhaust hood testing and certification in Folsom, California. CalHERS Energy provides TAB Certified professionals serving Folsom and the surrounding area since 2010. Call us today to schedule your project or request a free quote.
Phone: (916) 888-8770
Folsom enforces Title 24 energy compliance under Climate Zone 11 through the City of Folsom Building Division at 50 Natoma Street. Home to Intel's major fabrication and research campus, the headquarters of VSP Global, and a thriving commercial and retail corridor along East Bidwell Street, Folsom generates significant demand for semiconductor cleanroom HVAC certification, corporate campus commissioning, and Title 24 mechanical acceptance testing. The city is served by SMUD for electricity and PG&E for natural gas, with SMUD's commercial energy efficiency rebate programs requiring third-party TAB documentation. Folsom falls under Sacramento Metropolitan AQMD jurisdiction. Climate Zone 11's extreme summer heat drives active HERS testing for Folsom's substantial new residential construction in the Folsom Ranch master-planned community.
City of Folsom Building Division
The Folsom Building Division at 50 Natoma Street, Folsom, CA 95630, issues mechanical permits and enforces Title 24 energy code compliance. NRCA mechanical acceptance test certificates are required at final inspection for all commercial HVAC systems. ECC (formerly HERS) test results must be registered with an approved ECC Provider (such as CHEERS) before certificate of occupancy for residential projects. Sacramento Metropolitan AQMD Authority to Construct permits may be required concurrently for large commercial HVAC equipment. SMUD serves the electric utility territory and coordinates commercial rebate documentation.
Folsom is in Title 24 climate zone 12, the zone the California Energy Commission represents with Sacramento weather data. Zone 12 covers the Sacramento Valley, the Delta and the northern San Joaquin Valley: hot dry summers and cool wet winters, with cooling as the dominant load.
Kitchen exhaust fights the cooling system in hot weather, so a hood that captures poorly costs comfort and energy. Testing verifies airflow, capture and makeup-air balance for the system as installed.
Permits for exhaust hood testing work in Folsom go through the City of Folsom Building Division. Which office has jurisdiction depends on the exact address, so confirm it before the inspection is scheduled and ask which compliance documents your final inspection needs.
Commercial kitchens in Folsom are reviewed at permit by the building department and fire marshal, and food facilities answer to Sacramento County environmental health. Hood test reports are commonly requested by one of those offices.
Folsom is about 19 miles in a straight line from our Sacramento office. We serve Northern California and take larger projects statewide; send the address and scope and we will confirm coverage for your site.
Nearby cities we also serve include Orangevale (3 miles), El Dorado Hills (4 miles), Citrus Heights (7 miles), and Roseville (9 miles).
Other cities in Sacramento County that we serve include Sacramento, Elk Grove, Citrus Heights, Rancho Cordova, and Orangevale.
Exhaust Hood Testing nearby: Orangevale, El Dorado Hills, Citrus Heights, Roseville, Cameron Park, Rancho Cordova, Sacramento, Elk Grove
Folsom is in California Energy Commission climate zone 12 (Sacramento weather data represents it). The zone affects the inputs in the energy-code compliance documents for your project, so confirm the zone on your plans or compliance forms.
Permits for projects in Folsom go through the City of Folsom Building Division. Jurisdiction depends on the specific address, so confirm with the issuing office which inspections and compliance documents your project needs.
Yes. Folsom is about 19 miles from our Sacramento office. We serve Northern California and take larger projects statewide. Send the address, scope and timeline and we will confirm coverage and a quote.
Commonly the building department or fire marshal at permit and Sacramento County environmental health for food facilities. Ask the office for your address which report format it wants.
California commercial kitchens must comply with California Mechanical Code (CMC), International Mechanical Code (IMC), NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations), and local fire marshal requirements. UL 300 fire suppression systems require proper exhaust airflow for activation. Health departments also verify ventilation adequacy. Testing documentation is typically required for permit final, fire marshal inspection, and annual fire system certifications.
Capture velocity is the airflow speed at the hood's capture plane that draws cooking effluent (grease, smoke, steam) into the exhaust system. ASHRAE and IMC require minimum 50 FPM (feet per minute) for light-duty cooking, 75-100 FPM for medium-duty, and 100-150 FPM for heavy-duty cooking with solid fuel. Actual requirements depend on hood type (wall canopy, island, proximity), cooking equipment, and specific manufacturer ratings. We measure and document these values for code compliance.
Makeup air replaces the air exhausted by kitchen hoods to maintain proper building pressure. Without adequate makeup air (typically 80-90% of exhaust volume), kitchens experience negative pressure causing doors slamming, backdrafting of gas appliances (CO hazard), reduced exhaust performance, and uncomfortable drafts. California energy code also requires heated/tempered makeup air in certain climate zones. Our testing verifies proper makeup air balance.
Initial testing is required for new installations, major modifications, or change of cooking equipment type. Ongoing testing is recommended annually as part of fire system inspection and kitchen ventilation maintenance. Many jurisdictions require rebalancing documentation when fire suppression systems are recharged. Insurance carriers and franchisors may also mandate periodic verification for risk management.
Our testing includes: exhaust airflow measurement at each hood section, capture velocity readings across the hood face, makeup air volume verification, kitchen space pressure testing, temperature rise through hoods, documentation of hood and duct specifications, and fire suppression system interlock verification. We provide a certified report with all measurements for health department and fire marshal submissions.
Yes, smoke spillage can occur even with sufficient CFM if: capture velocity is inadequate (exhaust spread too thin), makeup air introduces excessive turbulence at cooking surfaces, HVAC supply registers create cross-drafts at hood edge, appliances are positioned incorrectly under hoods, or grease buildup on filters restricts airflow. Our testing identifies these issues and provides recommendations for correction.
Kitchen exhaust testing typically ranges from $500-$1,500 per kitchen depending on the number of hoods, equipment complexity, and documentation requirements. Multi-location restaurant chains often qualify for volume pricing. Emergency or expedited testing is available at premium rates. For an accurate quote, submit your project details including hood schedules and kitchen plans to Office@calherstab.com.
Type I hoods (grease hoods) are required over equipment producing grease-laden vapors: fryers, grills, ranges, ovens, woks. They include grease filters, fire suppression, and connect to dedicated grease exhaust ductwork. Type II hoods (heat/steam hoods) serve equipment producing only heat, moisture, or odors: dishwashers, steam tables, ovens without grease. Type II systems have less stringent fire protection requirements. Both require testing but have different airflow standards.
All CalHERS Energy services in Folsom